GENERATION DATA

The number of units is indicated for best operational efficiency at the design flow rate. It is evident from the flow rate records of the past 30 years that the flow rate is highly changing, therefore the units shall be operated with the available water level close to their maximum efficicency levels, while enabling safe maintenance and repair opportunities for the inoperative equipment.

Generation Capacity 18,86MW
Grid Connection Voltage 34,5kV
Short Circuit Ratio 1,0
Number of Units* 3
WATER DATA
Design Flow rate 83,10m3/sec
Unit Flow Rate 27,70 m3/sec
Gross Head 26,50m
Minimum Net Head 24,00m
Maximum Net Head 25,50m
Design Head 25,20m
PENSTOCK DATA
Type Spiral Welded Steel
Diameter 3200mm
Thickness 10mm
Length 75m
LOCATION OF PROJECT
35km To the City of Adiyaman Latitude 37_27_30_-37_28_30_-north
Longitude 38_09_10_-38_10_20_-east